中文官网

Safety Light Curtain Wiring Diagrams — The Complete Engineering Guide (DQC & All Series)

A light curtain wiring diagram is useful only when the device variant and safety function match the drawing. This guide retains the DQC five-core factory example and covers 32 wiring-reference checks: cable colours, NPN/PNP load positions, approved dual OSSD interfaces, feedback, reset, brand changes, supply design and commissioning. A DQC catalogue OUT is not automatically a safety-rated OSSD; the later safety-circuit examples describe functions, not universal terminals.

Content updated: 2026-09-06. Generated sketches with conflicting safety assumptions have been replaced by page-local reference panels. The original factory documents remain available as historical evidence, with known output/grounding label conflicts identified below; exact model manuals and machine validation are required before installation.

New to light curtains? For the fundamental operating principles behind everything on this page, start with How Does a Safety Light Curtain Work? — then come back here for the diagrams.
DAIDISIKE DQC Series Safety Light Curtain Dimensions
Figure 1: DAIDISIKE DQC Series Technical Dimensions and Components

Which wiring diagram do you need? Four questions that decide the circuit

These four checks choose the correct circuit family. An unanswered safety-interface question is a hold point, not an invitation to adapt a similar-looking drawing.

  1. NPN or PNP, and which logic? The DQC/DQA catalogue uses A = NPN NC, B = PNP NC, C = NPN NO and D = PNP NO; DQA J selects relay contacts. Confirm the complete ordering code and receiving input circuit. NPN sinks current and PNP sources current; they cannot be converted by swapping supply wires.
  2. What is the actual output integrity? Single OUT, dual OUT, relay contacts and approved OSSDs are not interchangeable descriptions. Obtain the exact safety rating and supported evaluation architecture before selecting a personnel-protective device.
  3. Where is required feedback evaluated? Identify the final switching elements and the approved EDM or equivalent monitoring arrangement. A missing input must not be bridged to clear a fault; use only a configuration explicitly permitted for the validated design.
  4. How is unexpected restart prevented? Select reset and restart interlocking from the risk assessment and device manual. A reset control must be outside the hazard zone with adequate visibility, and clearing the field or resetting must not itself start hazardous motion.

Transmitter or receiver? Identifying an unlabelled unit with a meter

A meter cannot recover a missing model identity or prove a safety rating. Keep an unidentified guard out of service until the manufacturer or machine documentation establishes its full model, cable and functions. Do not apply power to unknown conductors to discover a pinout.

Telling the transmitter from the receiver

Use the nameplate, original wiring schedule and manufacturer drawing first. The DQADQC catalogue standard DQC example has four transmitter cores and five receiver cores, but other output variants differ. Lamp meanings and conductor count are supporting clues, not universal identification rules. For a known unit, use only the specified test piece and controlled procedure with hazardous motion disabled—not a hand in the protective field.

Finding 0 V and the supply safely

Isolate and lock out hazardous energy before tracing conductors against the approved drawing. Identify supply positive, supply return, protective earth and shield as distinct functions. Continuity tests require isolation from external sources; live measurements, if necessary, belong to a qualified person's approved electrical test procedure. Never infer an unknown pin's purpose solely from a voltage reading.

Distinguishing an output from the sync conductor

In the DQC catalogue, black CP joins the transmitter/receiver synchronisation connection and white is OUT. The illustrated six-core dual-output variant labels white OUT1 and grey OUT2. Neither one nor two switching conductors proves monitored safety OSSDs; that requires the exact safety documentation and compatible evaluation.

Do not guess a damaged label or ambiguous cable. Obtain a traceable replacement drawing or replace the unidentified device through a validated design review. Once the unit is identified, use the light curtain alignment troubleshooting guide for its optical checks.

I. DQC Series 5-Core Cable Color and Function Definitions

This is the DQADQC catalogue standard DQC cable example, not a universal M12 assignment. Match the connector type, viewing direction, pin-to-core schedule and exact ordered cable before connection. Reversed supply can damage the unit.

Cable ColorSignal DefinitionFunction Description
Brown+12~24VDCPower Positive
Blue0V / GNDPower Negative
BlackCP (Control Signal)Synchronization signal line between transmitter and receiver
WhiteOUT (transistor output)Single switching output in this catalogue example; not evidence of a dual-channel safety-rated OSSD interface
Yellow-GreenShielding WireGround/shield conductor in this catalogue; terminate according to the exact product and machine EMC instructions, not interchangeably with 0 V
DQC standard cable: catalogue functions
+12/24 V supplyBrown positive; blue 0 V. Confirm the ordered voltage and cordset.
SynchronisationBlack CP joins the specified transmitter/receiver terminals.
OutputWhite OUT is a transistor output, not proof of a safety-rated OSSD.
Ground/shieldYellow-ground conductor follows the delivered cable drawing; PE and 0 V are not interchangeable.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

II. DQC 5-Core Wiring Diagrams — NPN and PNP

The DQC catalogue offers NPN and PNP switching variants selected by the A/B/C/D suffix. These two reference panels explain load position only. They do not establish a safety Type, PL/SIL or an approved protective-stop architecture.

1. Transmitter Wiring

The transmitter primarily emits the infrared beam. The brown wire connects to the 24VDC positive terminal, and the blue wire connects to 0V. The black wire (CP) must be connected to the receiver's black wire via the interface to achieve optical axis synchronization.

2. Receiver Wiring

The receiver detects signals and outputs logic based on light flux status. The brown wire connects to 24VDC, and the blue wire to 0V. The white wire (OUT) is the transistor switching output. Confirm the suffix, load and receiving input from the exact instructions; adding a relay coil does not turn a single output into a validated personnel-protective circuit.

DQC NPN: electrical load position
Current path when conducting+V → compatible load/input → white OUT → NPN transistor → 0 V.
LogicA/C suffix selects NC/NO in the catalogue; verify the required clear/blocked state.
Safety boundaryA single OUT driving a relay coil does not establish a personnel-protective stop.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

DQC PNP: electrical load position
Current path when conducting+V → PNP transistor → white OUT → compatible load/input → 0 V.
LogicB/D suffix selects NC/NO in the catalogue; do not infer polarity from a connector.
Safety boundaryLoad current, residual voltage and fault behaviour require exact interface evidence.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

DQC supply: identify +V and 0 V from the delivered manual and exact cable revision.

DQC output: the documented white OUT signal goes only to a compatible approved receiving interface. The colour, transistor polarity and output count do not establish a safety-rated OSSD function.

Grounding: identify protective earth, cable screen and circuit common separately. Use the released machine drawing and each equipment manual for bonding and shield termination; do not infer a universal connection among them.

Figure 5: DQC interface-identification reference, not a terminal diagram. It replaces a legacy illustration that incorrectly encouraged treating the white output as certified OSSD and combining shield, protective earth and 0 V. The original asset is retained in the repository, but is not presented here as wiring guidance.

Same drawings, three search names

Engineers arrive at this library searching for a safety light curtain wiring diagram, a light curtain sensor wiring diagram, or simply a light curtain wiring diagram — they are the same drawings. These search names overlap, but the devices do not share one pinout. The actual model determines colours, output integrity, synchronisation and permitted evaluator; a similar product name is not wiring compatibility.

III. Wiring by Series — Cores, Colors and Synchronization

Series names help locate a manual, but core count and connector appearance do not identify a safety architecture. The following six panels preserve the series-selection questions while avoiding unverified terminal assignments. The DQE white/black assignment was previously confirmed by the site owner for a physical manual; the delivered version still has to match.

Series and cable architecture review
DQC / DQAThe DQADQC catalogue documents wired CP and several output/controller variants.
DQO / DQEUse the exact unit and cable revision; conductor count does not prove output integrity.
JER / DQT4Confirm synchronisation, input functions, response and safety documentation separately; no all-series pin map.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

DQO: dual-output wiring review
IdentifyObtain the full model, cable drawing and receiver pinout.
EvaluateIf the specified variant has approved dual OSSDs, connect each to its own compatible safety input.
Do not inferCE, sync, reset and auxiliary lines are not interchangeable; no colour-only substitution.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

DQO seven-core identification record
Record before connectionList every core colour, pin number, function, source drawing and revision.
Resolve ambiguityAn unexplained or spare core stays unconnected only where the actual manual requires it.
Release conditionConfirm electrical function and safety interface; seven cores alone prove neither.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

DQE: channel assignment and variant check
Local evidence boundaryThe site owner previously confirmed white OSSD1 and black OSSD2 against a physical DQE manual.
Exact unit requiredDo not extend that mapping to another cable, suffix, or six/seven-core variant.
AcceptanceRecord the delivered manual revision and both receiving safety-input terminals.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

JER: synchronisation and output boundary
SynchronisationConfirm the optical-synchronised variant and its required unobstructed optical path.
ConnectionsUse its own transmitter/receiver cable drawing, not DQC CP colours.
Safety decisionNo dedicated sync cable or relay output proves a safety Type or complete stop function.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

DQT4: safety-interface design check
Product selectionReview the exact DQT4 safety documentation, output interface and response time.
EvaluatorVerify approved compatibility with the chosen safety relay or safety controller.
Reset / EDMLocate the functions in the approved design; do not assume DQSRN supplies reset or EDM.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

IV. OSSD Dual Channels and the EDM Feedback Loop

Keep documented safety outputs separately assigned to compatible safety inputs. Do not merge, series-wire or branch raw OSSDs to ordinary inputs. Supply protection, cable routing, pulse compatibility and final-element monitoring follow the exact equipment manuals and validated design; there is no universal fuse or separate-conduit rule per OSSD.

Dual OSSD and feedback: distinct paths
Detection pathOSSD1 → safety input 1; OSSD2 → safety input 2; neither is merged or paralleled to ordinary inputs.
Stop pathCompatible safety evaluation → validated final switching elements → required machine safe state.
Feedback pathWhere required: approved K1 NC mirror contact → K2 NC mirror contact → the designated EDM evaluator, in series.
Reset pathSeparate monitored reset only where specified; successful reset must not itself start hazardous motion.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Self-test pulses — and why a standard PLC input misreads them

Many safety outputs use short diagnostic pulses. Pulse duration, interval, permitted load and receiving-input tolerance are device-specific. A compatible safety input must interpret them as designed; an ordinary PLC filter cannot convert a standard input into a protective-stop evaluator.

OSSD pulses and input compatibility
What changesA safety output may use diagnostic test pulses with model-specific duration and interval.
Safety evaluationThe receiving safety input must be explicitly compatible; changing a standard PLC filter does not make it a safety input.
DiagnosticsUse a dedicated auxiliary/status interface instead of branching raw OSSDs to an ordinary PLC.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Keep diagnostics separate. Use a manufacturer-designated auxiliary/status signal or approved diagnostic communication for an ordinary PLC. Do not add a raw OSSD branch for status collection. Record both the output pulse specifications and the receiving safety input's compatibility evidence.
NPN / PNP: name the current direction
NPN outputSinks current; the compatible receiving load is towards +V.
PNP outputSources current; the compatible receiving load is towards 0 V.
Input commonRead the input circuit drawing. Manufacturer labels may name the sensor or the input, so the word NPN/PNP alone is insufficient.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

V. Connecting to a Safety Relay, a PLC, and the Reset Circuit

A documented dual-OSSD curtain needs compatible safety evaluation. For a candidate such as the DAIDISIKE DA31 , obtain the exact manual before assigning terminals, reset, feedback or compatibility. Catalogue contact counts and release times do not validate a complete circuit. For deeper treatment of each leg, use the dedicated guides: safety relay wiring in detail, NPN/PNP output logic and PLC integration, and the installation & wiring overview.

DA31 integration: hold until the manual matches
Required evidenceExact DA31 version, supported output/input type, test-pulse limits and approved circuit.
Not assumedS1/S2, SR/SRC, reset and EDM capabilities are not assigned by this reference panel.
Machine functionDetermine contactor/drive interfaces and full stopping time from the validated design, not a catalogue relay label.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

DA31 terminal and rating worksheet
RecordTerminal designation, function, voltage/current limits, contact utilization category and specified protection.
Reset / feedbackConfirm whether and where these are implemented; a status contact is not automatically an EDM input.
MismatchDo not wire from an old picture or transfer terminals from a different relay family.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Standard PLC: diagnostics on a separate path
Safety pathApproved OSSDs or approved safety communication → compatible safety controller → safe machine state.
Diagnostic pathManufacturer-designated auxiliary/status output or supported diagnostic communication → ordinary PLC → HMI.
Prohibited shortcutNo raw OSSD branch/merge/parallel to ordinary inputs, and no ordinary PLC program as the protective stop or safety reset.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Reset is not a restart command
SelectionUse the reset mode permitted by the risk assessment and exact safety-device manual.
LocationOutside the hazard zone with adequate visibility; address undetected presence separately.
TimingPress/release edge and timing are model-specific. Never bridge a fault or tape down a reset button.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

When you don't need a separate safety relay — relay-output and built-in-controller curtains

A validated machine design may use approved relay-output equipment or an integrated safety controller instead of a separate relay. The two catalogue options below describe electrical interfaces only: neither contact presence nor an external controller establishes that the required safety function is met.

DQA with the J output suffix — volt-free relay contacts

Ordering a DQA with J in the signal-output field replaces the transistor output with an internal relay giving volt-free contacts rated AC 250 V 10 A and DC 30 V 16 A in the catalogue. These headline ratings do not authorize every inductive load or prove a safety-contact architecture; verify utilization category, protection and the exact manual. The cable gains three function conductors in place of the single transistor output:

The contact behaviour is the part people get wrong. With the field clear, red-green is closed and red-white is open. With the field blocked, red-green opens and red-white closes. The catalogue does not establish the power-loss state or safety integrity of those contacts. Do not infer fail-safe operation from the clear/blocked table. Confirm the supply, CP and relay wiring for the delivered variant.

DQC with the DQCA or DQCA2 controller

The DQC series can be supplied with an external controller — DQCA for single-sided systems, DQCA2 for double-sided — which accepts the curtain and provides mains-voltage input (AC 110 V / 220 V) plus relay outputs in the catalogue example. That interface does not, by itself, authorize omitting a safety evaluator or switching a machine hazard. Confirm the complete device combination and safety design.

Judge the documented architecture, not transistor versus relay alone. A safety relay can use redundant monitored contacts; an ordinary transistor output can lack safety diagnostics. The DQA/DQCA catalogue does not settle that safety assessment. For a candidate DA31 module, confirm the actual approved input and machine circuit. Compare the interface questions in relay output vs OSSD solid-state output.

VI. Replacing Omron, Keyence, SICK or Pilz Curtains — Wiring Maps

A brand change requires a documented comparison of the complete protective function, not just a pin adapter. Start with match functions, never colors — similar M12 connectors do not guarantee identical pinouts. Full comparisons live on the dedicated pages for Omron F3SG-SR, Keyence SL-V / GL-R and SICK deTec / Pilz PSENopt.

Omron F3SG-SR replacement review
Keep functions visibleCompare exact detection capability, protective height, response, safety rating, interface and approved accessories.
DQC boundaryIts catalogue single OUT or dual OUT variants do not establish an equivalent OSSD safety interface.
DecisionHold the replacement until function-level documentation and machine validation are complete.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Keyence SL-V / GL-R replacement review
Variant firstConfirm the installed family, suffix and any muting, blanking, cascade or communications function.
No colour mappingCreate a terminal-to-function schedule from both current manuals; matched housings or range do not establish compatibility.
AcceptanceRecalculate full stopping distance and validate every affected safety function; no drop-in claim.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

SICK deTec / Pilz PSENopt replacement review
Safety envelopeRecord exact model functions and the required PL/SIL, detection and response.
InterfaceCheck pulses, reset, feedback, cable limits and connection orientation against both manuals.
Candidate boundaryDQC is not declared equivalent here; missing safety evidence is a hold, not an adapter-cable task.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

VII. Seven Wiring Mistakes to Check Before Commissioning

These are failure mechanisms to inspect, not a ranked dataset of customer incidents. A successful switching test alone does not validate fault detection. The related treatment is in the OSSD & EDM common-mistakes guide.

Wiring error 1: polarity selected by label alone
RiskA sourcing/sinking mismatch can prevent a valid input state.
Correct checkTrace the current path and receiving common in both manuals; PNP load towards 0 V, NPN load towards +V.
Safety limitElectrical switching compatibility does not prove safety suitability.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Wiring error 2: inventing channel-protection rules
RiskAn added fuse, shared connection or unapproved cable change can violate the device instructions.
Correct checkKeep the two safety signals separately assigned and follow the actual supply/output protection and routing requirements.
Do not assumeThere is no universal requirement for one fuse and one conduit per OSSD; use the approved architecture.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Wiring error 3: bypassing required feedback
RiskA missing or defeated feedback path can hide failure of a final switching element.
Correct checkValidate the required series mirror-contact feedback, its evaluator and timing under an approved test procedure.
No live shortingDo not short a contactor or feedback contact as a generic commissioning test.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Wiring error 4: merging safety channels
RiskJoining OSSD1 and OSSD2 or feeding both safety inputs from one output defeats the intended two-channel connection.
Correct checkOne specified output to each compatible safety input, with fault behaviour validated.
IsolationNo series E-stop contacts or parallel ordinary input branches in raw OSSD conductors.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Wiring error 5: ignoring EMC routing
RiskDrive, motor and welding cables can disturb sensor/control circuits.
Correct checkFollow the equipment and cable manuals for separation, shielding, bonding and permitted crossings.
No universal distanceA fixed 200 mm rule is not a substitute for the actual installation requirements.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Wiring error 6: treating PE, 0 V and shield as synonyms
RiskAn inappropriate bond or missing protective bond can create electrical or EMC problems.
Correct checkSeparate protective bonding, functional earth and supply return on the drawing.
TerminationOne-end or both-end shield termination is application/manual dependent; no universal 4 Ω rule is assigned here.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Wiring error 7: defeating deliberate reset
RiskA maintained or bypassed reset input can defeat restart interlocking, depending on the device.
Correct checkUse the specified monitored input and timing, address all presence hazards, and verify reset does not start motion.
FaultsA fault that will not reset requires diagnosis, not repeated cycling or a bridge.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

VIII. Mounting Distance and the Commissioning Trip Test

Wiring is only finished when the curtain is mounted at the ISO 13855 distance and the trip test is on record. A perfectly wired curtain mounted too close to the hazard still fails the risk assessment.

Mounting-distance worksheet
DistanceUse the applicable ISO 13855 method for approach geometry and effective detection capability.
Time TSensor + safety logic/communications + final-element response + machine stopping time, with required allowances and no double counting.
EvidenceMeasure machine stopping performance. Beam pitch and a catalogue sensor response are not the complete inputs.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Commissioning: controlled acceptance sequence
1 / 2Identify the exact devices and isolate hazardous energy; inspect wiring against the approved design.
3 / 4With hazards disabled, use the specified test piece along the complete required paths and boundaries; validate stop, interlock and faults under a planned safe procedure.
5 / 6Measure stopping performance and validate distance; record results, settings and authorization before service.
NeverDo not use a hand as the test piece, short a live contactor or assume clearing the field permits restart.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

IX. Importance of the Shielded Wire (Yellow-Green)

The DAIDISIKE DQC series is specially equipped with a yellow-green shielded cable to handle complex electromagnetic environments.

Supply and bonding design review
SupplyUse the device-specified voltage, tolerance, power-source class and available current.
ProtectionSelect supply and contact-circuit protection from each device manual and conductor/load requirements.
BondingDocument PE, functional earth/shield and 0 V separately; do not import DQE or relay figures into every curtain installation.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Use the actual EMC and protective-bonding design. Single-ended and multi-point shield connections serve different installations. Do not impose a universal one-end rule, earth-resistance target or fuse size on all curtains. The relay installation guide is a review aid, not authority to copy another model's ratings.

X. Cable Selection, Run Length and Voltage Drop

Supply drop is one possible installation fault. Use the actual sensor-pair current, supply tolerance, cable/connector limits and permitted load from the manufacturer. IEC 61131-2 does not establish a universal 20.4 V minimum for every light curtain.

The table is arithmetic only: hypothetical 0.3 A over a 40 m one-way copper run, with resistivity 0.0175 Ω·mm²/m. Round-trip voltage drop is ΔV = 2 × length × current × resistivity / cross-section. Temperature, connector losses, cable resistance tolerance and output/capacitance limits are not included. These are not maximum permitted run lengths.

ConductorResistanceIllustrative drop at 40 m / 0.3 AScope
0.25 mm²0.0700 Ω/m1.68 VIllustrative 40 m run only
0.34 mm²0.0515 Ω/m1.24 VIllustrative 40 m run only
0.50 mm²0.0350 Ω/m0.84 VIllustrative 40 m run only
0.75 mm²0.0233 Ω/m0.56 VIllustrative 40 m run only
1.00 mm²0.0175 Ω/m0.42 VIllustrative 40 m run only

Acceptance is broader than voltage drop. Check approved cordsets, maximum length/capacitance, flex and environmental ratings, routing and termination. Use proper connectors or specified terminals, not improvised joints. A closer supply or larger conductor is a design change that still needs reference, protection and EMC checks.

XI. M12 Connector Pinouts and Cordset Selection

A-coded M12 describes a connector interface, not a universal assignment of OSSD, reset or EDM signals. The table is an identification worksheet with common colour examples, not a pinout for installation. Use the exact device and cordset drawings and distinguish the mating-face view from the wiring-side view.

PinCordset colour4-pin function check5-pin function checkNotes
1Brown in many cordsetsRead device pinoutRead device pinoutConfirm mating-face or wiring-side view
2White in many cordsetsRead device pinoutRead device pinoutDo not assign OSSD2 from colour alone
3Blue in many cordsetsRead device pinoutRead device pinoutVerify return and permitted reference
4Black in many cordsetsRead device pinoutRead device pinoutBlack is CP on the DQC example, not universally OSSD1
5Varies by cordsetNot presentRead device pinoutMay be a signal or ground function; never guess

Check coding, position count, voltage/current rating, shielding, environmental seal and pin-to-pin continuity against the specified cordset. A different coding can carry power or communications, including an approved safety communication system; coding alone cannot tell you whether the overall circuit is safety-related. Never transfer a familiar colour or pin function to an unidentified connector.

XII. Muting and Blanking — Wiring the Exceptions

Muting and blanking both let material through a guard that would otherwise stop the machine, and they are wired very differently. Getting the distinction wrong is one of the few wiring errors that can silently remove protection while every LED stays green. The full decision treatment lives in muting vs blanking; what follows is the wiring.

Muting temporarily suspends a specified protective function under controlled application conditions. The permitted two- or four-sensor arrangement, direction, sequence/simultaneity, timing, load gaps and fault recovery belong to the exact approved system. Some curtains integrate muting; others require a suitable safety controller or module. Sensor count or a timer alone cannot prove a pallet rather than person entry.

Indication and override must follow the applicable requirements and device manual. Do not assume every relay has a muting output or that all lamps require the same monitoring. Validate stopped material, power interruption, failed/stuck sensors and any controlled recovery procedure without allowing undetected person access.

Blanking changes the treatment of selected beams. Fixed blanking may require continuous presence of the taught object and supplemental guarding against reaching through the resulting opening. Floating/reduced-resolution modes change effective detection capability. Use the actual mode's documented limits and reassess distance and access—not simply the original beam pitch. The safety distance calculator can organize inputs but does not approve the blanking application.

Four-sensor muting: application review
InputsApproved sensor arrangement → supported muting logic → the specified protective-device interface.
Access preventionValidate geometry, load gaps, direction, timing, sensor faults, stopped loads and access alongside or behind material.
Indication / overrideApply the exact system requirements. Sensor count alone does not distinguish a person from a pallet.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

Two-sensor muting: not a universal minimum
ModeSelect only a supported arrangement and direction for the actual conveyor and load.
GeometryCrossing point, sequence/simultaneity and coverage follow the specific approved mode, not a generic sketch.
AcceptanceTest foreseeable person access and fault/recovery cases; two crossed beams do not by themselves prove personnel protection.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

A supported muting architecture is required. Do not infer muting, reset or EDM from a relay's marketing mode list. DQSRN does not provide manual/automatic reset or EDM, and DA31 functions require its exact manual. Review muting vs blanking and the selected safety system's approved configuration before designing the access opening.

XIII. Cascading and Multi-Curtain Systems

Several openings require a coordinated safety function and diagnostics. The valid architecture depends on the actual devices, required fault behaviour, zoning and full response time—not a universal device-count or price threshold.

Use the full response chain. Include sensor, evaluation/communication, final-element response and the machine's measured stopping time with required allowances, avoiding double counting. Catalogue curtain/relay values alone omit the machine. For an approved cascade use its specified response calculation, then revalidate mounting distance.

Multi-curtain safety architecture
Approved cascadeUse only manufacturer-supported host/guest or cascade interfaces and their response calculation.
Separate evaluationIndividual safety inputs/evaluators can preserve diagnostics; combining safe outputs still requires an approved architecture and fault analysis.
Forbidden shortcutDo not wire raw transistor OSSDs in series or parallel. Revalidate whole-function response and distance after any change.

Functional reference, not a terminal-level installation drawing. Use the exact device manual and validated machine design.

XIV. Symptom-Based Wiring Troubleshooting

These six patterns organize possible causes; they are not frequency-ranked diagnoses. Read the exact fault code and manual with hazardous motion disabled. Similar lamp states can have different causes on different variants.

What you seePossible causesWhat to do
Receiver reports blocked/fault with a clear fieldPossible misalignment, obstruction, synchronization or device faultRead the exact fault code, identify both units and use the manual's alignment procedure with hazards disabled.
An implemented EDM function prevents resetPossible open wiring, wrong contact type, failed mirror contact or final-element faultIsolate and inspect the approved feedback circuit. Do not bridge it or short a live contactor.
Intermittent stop without intended entryPossible contamination, reflections, interference, movement or supply faultCheck the optical path and approved separation/routing; use scan codes only if supported by this model.
Unexpected input transitionsPossible pulse incompatibility, wiring fault or diagnostic interpretationVerify safety-input compatibility; ordinary PLC diagnostics use a separate auxiliary interface, not raw OSSDs.
Works locally but faults over the installed runPossible supply drop, connector loss, cable limit or reference mismatchMeasure under an approved safe procedure against the actual voltage/cable limits; do not assume a universal 20.4 V threshold.
Output state disagrees with interruptionPossible wrong suffix, merged channels, wiring short or device faultKeep hazardous motion disabled. Check the exact output definition and approved fault procedure; meter readings alone cannot prove safety integrity.

The last row is the one to take seriously. Bridging the two OSSDs, or feeding one OSSD into both relay inputs, produces a system that looks normal in a simple switching test while defeating the intended two-channel connection. A component Type or PL rating does not validate that altered circuit. Stop hazardous operation if the channel wiring is incorrect or unverified. Deeper diagnostics for the optical failure modes are collected in failure modes and false trips and EDM lockout diagnosis.

What should the multimeter read? Expected voltages, clear and blocked

Use a qualified person's approved electrical test procedure with hazardous motion prevented. The table distinguishes electrical conducting states from clear/blocked field states: the ordered NO/NC logic must be checked separately. Never use resistance/continuity mode on a circuit connected to an energized external source.

Conductor / functionReference observationWhat the reading cannot prove
Brown / supply positiveMeasure against the specified return under permitted load and compare with the delivered voltage limits.A nominal reading does not prove transient performance, polarity elsewhere or cable suitability.
Blue / supply returnCheck the approved reference arrangement and return continuity under safe isolated conditions.Zero volts measured against the same conductor is not evidence of a sound return or protective bond.
White / PNP OUTWhen conducting into a compatible load towards 0 V, the output is near supply less its residual drop. The DQADQC catalogue states a residual voltage below 1.5 V.Which field state causes conduction depends on the suffix. A meter cannot establish safety diagnostics or an OSSD rating.
White / NPN OUTWhen conducting with a compatible load towards +V, the output is near 0 V plus its residual drop; an unloaded OFF output may float.A floating reading is not a valid loaded switching test, nor proof of failure.
Black / CPTrace the documented transmitter-to-receiver connection with power isolated.A steady multimeter value cannot characterize synchronization signalling.
Ground / shieldInspect and test the connection required by the actual bonding and EMC design.Continuity at both ends does not by itself establish a fault; PE and 0 V are not interchangeable.
DQA J red–greenCatalogue: closed with field clear, open with field blocked. Test only using an approved low-energy method isolated from external circuits.The catalogue table does not establish the power-loss state, safety integrity or suitability as the sole stop path.
DQA J red–whiteCatalogue: open with field clear, closed with field blocked; exact external load and protection require the manual.Headline contact current/voltage is not an inductive-load or safety-function approval.
A meter does not validate a safety output pair. Similar readings on two outputs cannot prove independent fault detection or pulse compatibility. A channel that disagrees with its specified state can have several causes; keep the hazard disabled and follow the exact device's fault-diagnosis and validation procedure. Do not improvise live short-circuit tests.

Why won't my safety light curtain reset? An ordered diagnostic path

Keep hazardous operation disabled until the cause is understood. Work from identification and supply to the exact reset/feedback functions; stop at an unresolved check rather than bridging a terminal or repeatedly cycling power.

  1. Transmitter identity and power. Confirm its model, supply and manual-defined indications. An unlit lamp can indicate several conditions; colour alone does not diagnose the circuit.
  2. Receiver identity and power. Verify its own supply, cable and fault code under an approved safe test procedure.
  3. Alignment and synchronisation. Inspect the full optical path and the model's synchronization method. DQC wired CP must follow its drawing; an ambient-light incidence specification is not an alignment tolerance.
  4. Supported reset mode. Find which device implements reset and which mode the approved design uses. Do not assume generic terminal strapping or a DA31 function; DQSRN does not provide manual/automatic reset or EDM.
  5. Reset input behaviour. Compare the actual pushbutton, edge, duration and prerequisites with the specific manual. Do not substitute a maintained switch or a universal press–release timing pattern. Reset must not initiate hazardous motion.
  6. Required feedback circuit. Where EDM is implemented, inspect each required mirror contact and its wiring under isolation. Leaving a contact out can defeat monitoring; a broken wire or wrong contact can keep the loop open. See series NC feedback examples.
  7. Final-element fault. An unexpectedly open feedback path can mean a welded contactor, an auxiliary-contact problem or a wiring fault; it is not a diagnosis by itself. Use the EDM lockout guide and device instructions. Never bypass feedback to resume production.
  8. Channel discrepancy. Verify output type, wiring, permitted timing and receiving safety-input compatibility. Meter switching observations alone cannot validate the diagnostic behaviour.
  9. Shorts or damaged cabling. Inspect safely for crushed, bridged or loose conductors against the approved diagram. Which device detects a given fault depends on the exact architecture; do not assume every relay catches every fault.

XV. Selection Parameters and Recommendations

The DQADQC catalogue provides useful selection inputs, but they must match the delivered model and required safety function:

For more industry updates and technical guides, visit our Latest News Section.

Standards this page works to — and who may sign the installation off

Wiring a light curtain correctly is necessary but not sufficient. The documents below govern whether the resulting protective device is actually fit for the risk it is guarding against:

Scope of this guide. These diagrams are educational reference, not an installation instruction for your machine. The manual shipped with your unit takes precedence over anything here wherever the two differ. Commissioning a protective device is work for a competent person: the mounting distance must be recalculated from the measured stopping time of the actual machine, and the completed safety function must be validated before the guard is relied on. De-energise and apply lock-out/tag-out before landing any conductor. DAIDISIKE publishes this guide as the manufacturer of the DQ-series curtains described; it does not constitute a conformity assessment of your installation.

XVI. Summary

Identify the exact device and interface, keep approved safety channels separately assigned, and separate ordinary diagnostic signals from the protective-stop path. Verify required feedback/reset, electrical protection, cable limits and full stopping performance as one machine safety function. A neat connection or a successful switching test is necessary evidence, not proof of compliance.

Source documents and evidence boundaries

The DQC/DQA factory catalogue supports the specific colour, output-suffix, detection and electrical examples above; it does not supply a complete safety-function assessment. For interface and commissioning principles, consult the exact manufacturer's instructions, such as the SICK deTec4 Core operating instructions. A Phoenix Contact M12 cordset drawing illustrates why connector face and cordset assignment must be recorded separately from the device function. Application review uses the applicable IEC 62046:2026 and ISO 13855:2024 methods alongside machine-specific requirements.

Choose DAIDISIKE (戴迪斯科) — Professional Safety Solutions for Modern Industry.

DAIDISIKE Tech & Video Center

Advanced Sensor Solutions for Industrial Safety and Automation

DAIDISIKE Corporate Profile

Discover our commitment to precision engineering and manufacturing.

Safety Interlock DX Series

Real-world application for advanced machine safeguarding.

AGV LiDAR DLD30T-5N — 30 m at 90% remission / 10 m at 10% remission

Enhanced perimeter security and collision prevention solutions.

Vehicle DQLV Light Curtains

Optimized for toll stations and weighbridges profiling.

Measuring DQL Series 3D

Dimensional measurement and object positioning principles.

DQC Universal Grating

Installation guide for hand & finger safeguarding.

Waterproof DQR Series

Performance under high-pressure washdowns.

Color Mark Sensors

Intelligent recognition for high-speed packaging lines.

Strip DK-D461 Sensors

Advanced background suppression for irregular shapes.

Area DQSA Protection

Cost-effective side safeguarding using mirror reflection.

OUR PRODUCTSFACTORY TOUROUR TEAMVIDEO CASE STUDIESSOLUTIONS & FAQ

Frequently Asked Questions

What do the wire colours mean on a DQC 5-core safety light curtain cable?

The DQADQC catalogue standard DQC example shows brown supply positive, blue 0 V, black CP synchronisation, white transistor OUT and a ground/shield conductor. White OUT is not evidence of a dual-channel safety-rated OSSD interface. Confirm the exact suffix, cable and manual before wiring.

How do I wire the transmitter and receiver?

Confirm the exact transmitter/receiver pair and supplied cable drawing. On the documented DQC wired-sync example, brown and blue supply each unit and black CP joins the pair; the receiver output is wired only to a compatible documented interface. Other series and optical-sync variants differ.

How do you wire a safety light curtain to a safety relay?

First verify that the exact curtain and relay are approved for the required safety function and electrically compatible. Connect each specified OSSD to its own safety input, then implement final-element feedback and reset where required by the validated design. Fuse ratings, terminals and reset timing are model-specific; do not assume DA31 or DQSRN functions from a generic diagram.

What is the OSSD output on a light curtain?

An OSSD is an output signal switching device associated with a protective device. Many safety light curtains provide two monitored solid-state outputs, but an ordinary NPN/PNP OUT or two switching conductors do not establish a safety-rated OSSD pair. Follow the exact safety-interface documentation; never merge two OSSDs into one input.

Can I connect a safety light curtain directly to a standard PLC?

A standard PLC is not the protective-stop evaluator. Use a manufacturer-designated auxiliary/status output or supported diagnostic communication for its HMI and diagnostics. Do not parallel or branch raw OSSDs to ordinary PLC inputs. The safety path uses compatible safety-rated evaluation and validated final elements.

What is the difference between NPN and PNP light curtain wiring?

NPN sinks current with the receiving load towards the positive supply; PNP sources current with the receiving load towards 0 V. Check the receiving input circuit rather than relying on the words NPN or PNP, since manufacturers may name the input by its own circuit or its compatible sensor.

Why does my light curtain trip randomly?

Possible causes include alignment, contamination, reflections, supply drop, synchronization, EMC interference or interface incompatibility. Keep the hazardous function stopped while investigating; follow the exact device fault code and routing/bonding instructions. Do not assume one shield termination or a universal cable-separation distance.

Why is the shielded (yellow-green) wire important?

A shield or functional-earth connection can help control interference, but protective earth, shield and 0 V have different roles. Follow the delivered product and machine EMC design for termination; a blanket single-end or both-end rule is not valid for every installation.

What should I check before powering on?

Isolate and lock out hazardous energy before wiring. Confirm exact models and pin assignments, supply, protection, safety-input compatibility, required feedback/reset, cable condition and bonding. Commission through a controlled validation procedure with the specified test piece and measured machine stopping performance before service.

How do I select the right parameters for my application?

Use the specified detection capability, not beam pitch, and confirm protective height, operating range, safety rating, full-function response and environmental suitability. Apply the relevant ISO 13855 method and machine-specific requirements; wiring compatibility alone does not establish a safe installation.