中文官网

Safety Light Curtain Wiring Diagrams — The Complete Engineering Guide (DQC & All Series)

In industrial automation production lines, the correct wiring of safety light curtains not only ensures normal equipment operation but also serves as the first line of defense for operator safety. This guide collects 32 labeled wiring diagrams in one place: 5-core and 7-core color codes, NPN and PNP hookups, dual-channel OSSD with EDM feedback, safety relay and PLC connections, brand-replacement mapping, the seven wiring mistakes we see most in the field, and the commissioning trip test. As a leading domestic sensor manufacturer, DAIDISIKE (戴迪斯科) DQC series universal safety light curtains have gained market recognition for their high reliability and simplified installation process — the DQC 5-core method opens the guide, followed by every other series.

Free download — Safety Light Curtain Wiring Handbook (PDF)

All 32 diagrams from this guide in one printable file: color codes, NPN/PNP hookups, OSSD + EDM loops, relay and PLC wiring, the seven costly mistakes, and the commissioning test sheet.

⬇ Download the PDF
New to light curtains? For the fundamental operating principles behind everything on this page, start with How Does a Safety Light Curtain Work? — then come back here for the diagrams.
DAIDISIKE DQC Series Safety Light Curtain Dimensions
Figure 1: DAIDISIKE DQC Series Technical Dimensions and Components

Which wiring diagram do you need? Four questions that decide the circuit

Every diagram further down this page is one combination of four answers. Settle these first and you will know which figure to scroll to instead of reading all thirty-two.

  1. NPN or PNP? This is fixed by the model suffix at the point of order, not by wiring. On DQC and DQA the fourth field of the part number carries it: A = NPN normally-closed, B = PNP normally-closed, C = NPN normally-open, D = PNP normally-open, and on DQA J = volt-free relay output instead of a transistor. Read the nameplate before you plan the panel — a DQC08/40-2801AA is an NPN NC unit and will not drive a sinking input correctly.
  2. Safety relay, safety PLC, or a curtain with a built-in controller? A transistor-output curtain always needs something to evaluate its two channels. A DQA ordered with the J suffix, or a DQC paired with the DQCA / DQCA2 controller, already contains the relay stage.
  3. Is EDM used or bridged? External Device Monitoring watches the contactors for welded contacts. If your safety relay supports it and you are switching contactors, wire it. If you are not using it, bridge the terminal per the relay manual — never leave it floating.
  4. Automatic, manual or monitored reset? Automatic restart is only permissible where nobody can stand inside the guarded zone undetected. Anything else needs a reset button mounted outside the guarded area with a clear view of it.

Transmitter or receiver? Identifying an unlabelled unit with a meter

The single most common real-world starting point is a curtain already bolted to a machine with the label worn off and no manual in the cabinet. None of the wiring guides currently ranking for this query address it. Here is the procedure, in the order that keeps you safe.

Telling the transmitter from the receiver

On DQC and DQA the two sticks are not interchangeable and differ in three observable ways. The transmitter carries fewer conductors — the DQC datasheet specifies four cores at the projector and five at the receiver, because only the receiver has an output to send anywhere. The indicator behaviour differs: the transmitter has a single red power lamp that lights as soon as it is energised and never changes, while the receiver's indicator is the diagnostic one — green when every beam is clear, red when the field is broken. Finally the receiver is the one whose state changes when you pass your hand through the field. If nothing on a stick reacts to an interruption, it is the transmitter.

Finding 0 V and +24 V safely

Work de-energised first. With the supply isolated and locked off, use the continuity range to find which conductor is bonded to the panel earth stud — on DAIDISIKE cable that is the yellow-green shield, and it should read near zero ohms to PE. Then restore power and, with the meter on DC volts and the black probe on the panel 0 V rail, measure each remaining conductor in turn. The supply pair is unmistakable: one conductor sits at roughly +24 V and does not move regardless of whether the field is clear or blocked, and one sits at 0 V. On DAIDISIKE cable these are brown and blue respectively.

Distinguishing an output from the sync conductor

Of the conductors that remain, the output changes state when you break the beam and the sync line does not. On the DQC the synchronisation conductor is black, labelled CP, and it is butt-jointed directly between transmitter and receiver — it goes to the other stick, not to your panel, so if you trace a conductor and it terminates at the opposite unit you have found CP. The white conductor is the one that switches. On a six-core DQC dual-output unit there are two switching conductors: white is OUT1 and grey is OUT2.

Do not skip the meter step on a safety circuit. Identifying by colour alone is exactly how channels get swapped. A curtain wired with its two outputs crossed can still look healthy on the indicator lamps while failing to give the dual-channel redundancy the rating depends on. If the unit cannot be identified with confidence, replace it rather than guess — and see light curtain alignment troubleshooting once it is powered.

I. DQC Series 5-Core Cable Color and Function Definitions

DQC series safety sensors connect via aviation connectors to M12 five-core cables. Before wiring, strictly verify cable colors and their corresponding electrical functions to prevent circuit burnout from reverse polarity.

Cable ColorSignal DefinitionFunction Description
Brown+12~24VDCPower Positive
Blue0V / GNDPower Negative
BlackCP (Control Signal)Synchronization signal line between transmitter and receiver
WhiteOSSD OutputSafety switch signal output (connects to relay or PLC)
Yellow-GreenShielding WireSuppresses electromagnetic interference; connects to ground
5-core wire color code chart for DQC safety light curtain: brown +24VDC, blue 0V, black CP sync, white OSSD, yellow-green shield
Figure 2: 5-core wire color code at a glance — print this for the junction box

II. DQC 5-Core Wiring Diagrams — NPN and PNP

The DQC series typically supports both NPN and PNP logic output modes (output logic follows the A/B/C/D model suffix). The NPN single-output connection is the most common, so it comes first; the PNP variant differs only in where the load sits.

1. Transmitter Wiring

The transmitter primarily emits the infrared beam. The brown wire connects to the 24VDC positive terminal, and the blue wire connects to 0V. The black wire (CP) must be connected to the receiver's black wire via the interface to achieve optical axis synchronization.

2. Receiver Wiring

The receiver detects signals and outputs logic based on light flux status. The brown wire connects to 24VDC, and the blue wire to 0V. The white wire (OSSD) is the core output line, typically connected to a safety relay (e.g., K1 load) to control motor disconnection.

DQC safety light curtain 5-core NPN wiring diagram with transmitter, receiver, CP sync line and OSSD output to K1 relay
Figure 3: DQC standard NPN single-output wiring — load between +V and OSSD
DQC safety light curtain 5-core PNP wiring diagram showing load connected between OSSD output and 0V
Figure 4: DQC PNP variant — load between OSSD and 0 V
DQC series five-core wiring diagrams NPN
Figure 5: Factory catalogue wiring sheet for the DQC series

Same drawings, three search names

Engineers arrive at this library searching for a safety light curtain wiring diagram, a light curtain sensor wiring diagram, or simply a light curtain wiring diagram — they are the same drawings. Whether your paperwork calls the device a safety light curtain, a light curtain sensor or a light barrier, the cable colors, OSSD outputs and relay hookups on this page apply unchanged; only the model table you order from differs.

III. Wiring by Series — Cores, Colors and Synchronization

Different DAIDISIKE series use different cable architectures: the economical JER transmitter needs only 3 cores because synchronization is optical, while the Type 4-architecture DQT4 runs a 9-core cable for its redundant PNP OSSD pair with EDM. The chart below is the fastest way to know what you will find in the junction box before the panels are even open.

Reference chart of DAIDISIKE safety light curtain series cable core counts and synchronization types, DQA to MK
Figure 6: Cable cores and synchronization across every series
DQO series 7-core dual OSSD wiring diagram with white OSSD1, green OSSD2 and red CE self-check line
Figure 7: DQO 7-core dual-OSSD wiring — white OSSD1, green OSSD2, red CE self-check
7-core wire color code chart for DQO safety light curtain including dual OSSD and CE line
Figure 8: DQO 7-core color code table
DQE 6-core and 7-core wire color chart with caution about OSSD channel order
Figure 9: DQE 6/7-core colors — note the caution on OSSD channel order
JER safety light curtain wiring: 3-core transmitter and 5-core receiver with optical synchronization, no sync cable
Figure 10: JER optical-sync architecture — no sync cable between Tx and Rx
DQT4 Type 4 safety light curtain 9-core PNP-only wiring architecture with dual OSSD and EDM
Figure 11: DQT4 9-core PNP-only architecture with dual OSSD + EDM

IV. OSSD Dual Channels and the EDM Feedback Loop

Everything downstream of the receiver depends on two rules: the two OSSD channels stay fully independent (own fuse, own routing), and the contactors report back through EDM so a welded contact blocks the restart. The two diagrams below are the heart of this entire guide — if you internalize them, every relay and PLC hookup that follows is just detail.

Dual-channel OSSD wiring with EDM feedback loop through K1 and K2 normally-closed auxiliary contacts
Figure 12: Dual-channel OSSD with EDM feedback — the complete safety loop

Self-test pulses — and why a standard PLC input misreads them

An OSSD does not simply sit high while the field is clear. It briefly pulls itself low, over and over, and watches whether the line actually follows. That is how the curtain detects a short to +24 V, a short to 0 V or a short between the two channels — faults that a simple on/off output could never reveal. A safety input expects those pulses and ignores them. A standard PLC input often does not: if its filter is faster than the pulse, it reports every self-test as a real interruption, and you get phantom transitions and nuisance trips on a curtain that is behaving perfectly.

OSSD self-test pulse train compared with a standard PLC input filter, showing why a healthy safety output reads as chattering on a non-safety input
Figure 30: OSSD self-test pulses vs a standard PLC input filter — the same healthy output, two different readings
The two numbers you need are not ours to publish. The pulse width belongs to your curtain's datasheet and the input filter time to your PLC's manual; the diagram above labels both axes symbolically for that reason. What is universal is the rule: a standard PLC input may monitor an OSSD for status, but it must never sit in the stop path.
NPN versus PNP OSSD output wiring comparison showing load position relative to +24V and 0V
Figure 13: NPN vs PNP — where the load goes, and which polarity the input common takes

V. Connecting to a Safety Relay, a PLC, and the Reset Circuit

The canonical downstream hookup is a dual-OSSD curtain into a safety relay such as the DAIDISIKE DA31 (3 force-guided NO contacts + 1 NC auxiliary, release < 30 ms). For deeper treatment of each leg, this hub links out to the dedicated guides: safety relay wiring in detail, NPN/PNP output logic and PLC integration, and the installation & wiring overview.

Complete DQE light curtain to DA31 safety relay wiring diagram with OSSD1/OSSD2 into S1/S2, EDM feedback and SR/SRC reset
Figure 14: DQE → DA31 complete loop — power, S1/S2, safety contacts, EDM and reset
DA31 safety relay terminal map: S1 S2 inputs, 13/14 23/24 33/34 NO contacts, 41/42 NC auxiliary, SR/SRC reset, contact ratings
Figure 15: DA31 terminal map and contact ratings
Light curtain status monitoring wiring into Mitsubishi FX5U or Siemens S7-1200 PLC inputs X0 to X3
Figure 16: Status monitoring into a standard PLC — monitoring only, never the stop path
SR SRC reset terminal wiring: shorted for auto reset, open with momentary button for manual reset
Figure 17: Reset modes at SR/SRC — auto vs manual

When you don't need a separate safety relay — relay-output and built-in-controller curtains

Not every installation needs a DIN-rail safety relay. Two DAIDISIKE options put the relay stage inside the product, which removes a component from the panel and a pair of terminations from the job.

DQA with the J output suffix — volt-free relay contacts

Ordering a DQA with J in the signal-output field replaces the transistor output with an internal relay giving volt-free contacts rated AC 250 V 10 A and DC 30 V 16 A. The cable gains three function conductors in place of the single transistor output:

The contact behaviour is the part people get wrong. With the field clear, red-green is closed and red-white is open. With the field blocked, red-green opens and red-white closes. The stop function therefore rides on the red-green pair, because that is the pair that opens on detection and on loss of power — the fail-safe direction. Brown, blue and the black CP sync line are unchanged from the transistor version.

DQC with the DQCA or DQCA2 controller

The DQC series can be supplied with an external controller — DQCA for single-sided systems, DQCA2 for double-sided — which accepts the curtain and provides mains-voltage input (AC 110 V / 220 V) plus relay outputs, so the curtain can drop a machine circuit without a separate 24 V safety relay in the panel.

What you give up. A relay output is a single electromechanical contact, not two independently monitored solid-state channels. You lose OSSD cross-fault detection, you lose the test-pulse diagnostics that reveal a shorted output before it matters, and you lose the dual-channel structure that architectures above the simplest categories are built on. Relay-output curtains suit retrofits onto older machines that expect a dry contact and lower-demand applications; where a risk assessment calls for dual-channel monitoring with EDM, use a transistor-output curtain into a DA31 safety relay module and see relay output vs OSSD solid-state output.

VI. Replacing Omron, Keyence, SICK or Pilz Curtains — Wiring Maps

Most rewiring jobs we support are brand swaps on running machines. The safe method is always the same: match functions, never colors — similar M12 connectors do not guarantee identical pinouts. Full comparisons live on the dedicated pages for Omron F3SG-SR, Keyence SL-V / GL-R and SICK deTec / Pilz PSENopt.

Omron F3SG-SR to DAIDISIKE DQC replacement wiring function mapping table
Figure 18: Omron F3SG-SR → DQC function-to-function map
Keyence SL-V and GL-R to DAIDISIKE DQC replacement wiring checklist
Figure 19: Keyence SL-V / GL-R → DQC replacement checklist
SICK deTec and Pilz PSENopt to DAIDISIKE DQC replacement wiring checklist
Figure 20: SICK deTec / Pilz PSENopt → DQC replacement checklist

VII. The Seven Wiring Mistakes That Cost the Most

Each of these has reached our support inbox more than once. They all pass a quick bench test — and fail on the machine, sometimes silently. The full write-up lives in the OSSD & EDM common-mistakes guide.

Wiring mistake: mixing NPN and PNP sensors on one input common
Wiring mistake: OSSD1 and OSSD2 sharing one fuse and cable loom
Wiring mistake: EDM feedback loop not wired, welded contactor goes undetected
Wiring mistake: merging OSSD1 and OSSD2 into one relay input destroys redundancy
Wiring mistake: signal cables routed parallel to VFD motor power causing nuisance trips
Wiring mistake: shield floating or grounded at both ends instead of single-point ground
Wiring mistake: latched reset button causes unattended machine restart

VIII. Mounting Distance and the Commissioning Trip Test

Wiring is only finished when the curtain is mounted at the ISO 13855 distance and the trip test is on record. A perfectly wired curtain mounted too close to the hazard still fails the risk assessment.

ISO 13855 safety distance formula S equals K times T plus C for light curtain mounting
Figure 21: S = K × T + C — response time (≤ 15 ms on DQ-series) is part of the wiring math
Six-step safety light curtain commissioning trip test sequence
Figure 22: The 6-step commissioning trip test — run it after every rewiring or brand swap

IX. Importance of the Shielded Wire (Yellow-Green)

The DAIDISIKE DQC series is specially equipped with a yellow-green shielded cable to handle complex electromagnetic environments.

24V PELV supply architecture for a safety light curtain: series fuse, 4-core transmitter, 5-core receiver and shield earthed at a single point on the cabinet PE bar
Figure 31: 24 V PELV supply, series fuse and the single-point earth — the power architecture ahead of the curtain
One earth, not two. Bonding the shield at both ends creates a ground loop, and a ground loop injects exactly the noise the shield exists to reject. Land it at the cabinet PE bar and leave the far end floating. The supply-side figures shown — 5 A gL/gG, ripple ≤ 10 %, earth resistance ≤ 4 Ω — are the values published for the DQE to DA31 safety relay installation; a relay's output contacts carry their own separate fuse, so do not reuse one rating for both.

X. Cable Selection, Run Length and Voltage Drop

The most common cause of a curtain that passes a bench test and then faults on the machine is not the curtain — it is the cable. A light curtain pair draws roughly 300 mA, and every metre of conductor between the cabinet and the receiver drops a little of the 24 V it needs. IEC 61131-2 sets the floor at 24 V −15%, or 20.4 V; below that the receiver's internal supervision starts declaring faults that look exactly like optical problems.

The drop is a round trip — current goes out on brown and back on blue — so a 40 m installation means 80 m of copper. With annealed copper at 0.0175 Ω·mm²/m, the usable run length falls out directly from conductor cross-section:

ConductorResistanceMax run @ 300 mATypical use
0.25 mm² (AWG 24)0.070 Ω/m25 mBench work and in-panel jumpers only
0.34 mm² (AWG 22)0.052 Ω/m35 mStandard factory cordsets — most installs
0.50 mm² (AWG 20)0.035 Ω/m50 mLong guard perimeters, palletizer cells
0.75 mm² (AWG 18)0.023 Ω/m80 mCross-plant runs, outdoor perimeter
1.00 mm² (AWG 17)0.017 Ω/m105 mLong-range through-beam, remote cabinets

Three rules that are not optional. Never run OSSD conductors in the same duct as motor or VFD cabling — the switching transients couple straight into the safety channel and produce trips no one can reproduce. Never extend a cable with a twisted joint in a junction box; use a moulded cordset or a proper terminal. And where a run exceeds the figures above, move the 24 V supply closer rather than accepting the drop — a local DIN-rail supply is cheaper than a week of intermittent-fault hunting.

XI. M12 Connector Pinouts and Cordset Selection

Flying-lead curtains are wired by colour; connectorised curtains are wired by pin number, and the two do not always agree. The pin assignment below is fixed by IEC 61076-2-101 for A-coded M12 and is the same on every compliant device. The colours are the conventional cordset colours — usually right, never guaranteed.

PinCordset colour4-pin5-pinNotes
1Brown+24 VDC+24 VDCSupply — same on both variants
2WhiteOSSD 2 / inputOSSD 2Second safety channel
3Blue0 V0 VSupply return — same on both
4BlackOSSD 1OSSD 1First safety channel
5GreyEDM / test / selectOnly on 5-pin; function is model-specific

Two practical points. First, A-coded is for signals, not power — if you find a B, D or L-coded connector on a guard, it is a fieldbus or a motor feed and it does not belong on the safety circuit. Second, the pin-5 function is the one that varies between manufacturers: on some models it is EDM feedback, on others a test input or a range-select line. On a brand swap this is the single most likely pin to be wrong, which is why section VI above insists on matching functions rather than pin numbers.

XII. Muting and Blanking — Wiring the Exceptions

Muting and blanking both let material through a guard that would otherwise stop the machine, and they are wired very differently. Getting the distinction wrong is one of the few wiring errors that can silently remove protection while every LED stays green. The full decision treatment lives in muting vs blanking; what follows is the wiring.

Muting suspends the whole protective field for a defined window while a pallet passes. It requires at least two independent muting sensors arranged so that no single object — least of all a person — can trigger them in a valid sequence. The standard arrangements are crossed-beam (two photoelectric sensors whose beams intersect at the guard line) or the four-sensor T/L pattern for bidirectional conveyors. The muting inputs go to the safety relay or muting module, never to the curtain itself, and the sequence logic enforces both an order and a maximum time. A muting window that never times out is not muting — it is a bypass.

A muting indicator lamp is mandatory, not a convenience: it tells anyone approaching that the guard is currently suspended. Most safety relays provide a dedicated lamp output with filament monitoring, and where they do not, the lamp must be separately supervised.

Blanking is different — it disables specific beams permanently (fixed blanking, for a fixture that always occupies the field) or lets a defined object move through a window of beams (floating blanking). Blanking is configured on the curtain, not wired externally, and it carries a hard consequence: blanking beams degrades the effective resolution. A 14 mm finger-protection curtain with two beams blanked no longer detects a finger at that height, and the ISO 13855 safety distance must be recalculated against the new resolution. Run the numbers again in the safety distance calculator before the machine goes back into production.

Four-sensor T-pattern muting layout showing muting inputs, muting lamp output and override input labelled by function
Figure 32: Four-sensor T-pattern muting — sensor arrangement, muting lamp and override, labelled by function
Two-sensor crossed-beam muting layout with the crossing point ahead of the protective field
Figure 33: Two-sensor crossed-beam muting — the minimum arrangement that can tell a pallet from a person
Muting is geometry, not a timer. What proves "pallet, not person" is the order and overlap of the muting sensors, and the muting lamp is mandatory so anyone approaching can see the field is suspended. Both diagrams label ports by function rather than terminal number, because no relay in this catalogue offers a muting mode — the DA31 and DQSRN each provide four selectable input modes (E-stop, light-curtain OSSD, safety door, two-hand control) and muting is not among them. Take terminal designations, the simultaneity window and any timeout from the manual of the muting module you actually specify, and see muting vs blanking to confirm which one your line needs.

XIII. Cascading and Multi-Curtain Systems

Guarding a cell on three sides raises a question the datasheets rarely answer: one relay per curtain, or all curtains into one relay? Both are valid; they trade cost against diagnostics.

Response times add up. The stopping-performance figure in an ISO 13855 calculation is the whole chain, not the curtain alone: curtain response + relay release + contactor drop-out + the machine's own stopping time. A 15 ms curtain behind a 30 ms relay and a 40 ms contactor is an 85 ms chain before the machine has begun to stop. Series-cascading several curtains adds each stage's response as well — recalculate the safety distance for the assembled system, never from the curtain datasheet.

Cascading safety light curtains: curtains in series into one relay compared with one safety relay per curtain, with the stop-time budget
Figure 34: Curtains in series into one relay vs one relay per curtain — diagnosis and response time against panel cost

XIV. Symptom-Based Wiring Troubleshooting

Most commissioning faults resolve to one of six patterns. Read the LED states first — the curtain is usually telling you exactly what is wrong before any meter comes out.

What you seeMost likely causeWhat to do
Receiver red, transmitter green, beam path clearOptical misalignment, or transmitter and receiver swapped end-for-endRe-aim until the alignment LED goes solid; confirm the transmitter is the unit with no OSSD wires
OSSD will not turn on, EDM lamp litEDM loop open — a contactor has welded, or the feedback contacts are wired NO instead of NCMeasure continuity across the feedback path with the contactors de-energised; it must be closed
Machine stops intermittently, no one in the guardOptical interference from a second curtain, a reflective surface, or welding arc flashSet adjacent pairs to opposing scan codes, add anti-reflection baffles, re-check the 130 mm reflective-surface clearance
OSSD toggles rapidly at power-up then settlesNormal OSSD test pulsing being read by a standard PLC input as a real transitionRoute OSSD to a safety relay or safety input card; a standard input must be monitoring-only
Curtain works on the bench, faults on the machineVoltage drop over the installed cable run, or 0 V referenced to a different supply than the relayMeasure supply at the receiver under load — below 20.4 V, increase conductor size per the table above; bond all 0 V to one point
Both channels stuck on even with the beam blockedOSSD pair bridged, or a single OSSD paralleled into both relay inputsStop production immediately. Each OSSD must land on its own relay input; this defeats the dual-channel architecture

The last row is the one to take seriously. Bridging the two OSSDs, or feeding one OSSD into both relay inputs, produces a system that looks completely normal — green LEDs, machine runs, guard appears to work — while the dual-channel architecture that earns the Type 4 / PL e rating no longer exists. A single fault will then go undetected. If you find this on a running machine, stop it. Deeper diagnostics for the optical failure modes are collected in failure modes and false trips and EDM lockout diagnosis.

What should the multimeter read? Expected voltages, clear and blocked

Measure with the black probe on the panel 0 V rail and the meter on DC volts, with the machine isolated so an unexpected start cannot injure anyone. "Clear" means every beam unobstructed and the receiver indicator green; "blocked" means the field interrupted and the indicator red.

ConductorField clearField blockedWhat it tells you
Brown (supply +)+24 V DC+24 V DCUnchanging. If it sags when the field is broken the supply is undersized or shared with an inductive load.
Blue (0 V)0 V0 VAny standing voltage here means a shared or broken 0 V return — fix before going further.
White — PNP output, NO type≈ +24 V (within ~1.5 V of supply)≈ 0 VA sourcing output pulls up to supply less its saturation drop. The DQC/DQA spec allows up to 1.5 V, so ~22.5 V on a 24 V rail is healthy, not faulty.
White — NPN output, NO type≈ 0 V (within ~1.5 V of 0 V)Floats to near supplyA sinking output only pulls down. Read it with the load connected — measured open-circuit it floats and the numbers mean nothing.
Black (CP sync)Not a steady DC level — do not judge it by voltageCP is butt-jointed between transmitter and receiver. Verify it with continuity between the two units, de-energised.
Yellow-green (shield)≈ 0 V, and near 0 Ω to PE at its single bonding pointContinuity to PE at both ends means a ground loop — land it at one end only.
Red–green pair, DQA relay (J) versionClosed (continuity)OpenVolt-free contacts, so measure continuity, not volts. Red-green is the normally-closed pair and is the one that carries the stop function.
Red–white pair, DQA relay (J) versionOpenClosed (continuity)The normally-open pair, for signalling and indication. Contact rating is AC 250 V 10 A / DC 30 V 16 A.
Reading both outputs identically is not proof the curtain is healthy. Two channels that switch together look correct on a meter but tell you nothing about cross-fault detection. Confirm each OSSD drops independently during the trip test, and treat a channel that is stuck at supply while the other switches as a cross-fault to +24 V rather than a dead output.

Why won't my safety light curtain reset? An ordered diagnostic path

Work down this list in order and stop at the first step that fails. The sequence matters: each check assumes the ones above it passed, and jumping to the middle is how an afternoon disappears.

  1. Transmitter powered? Its red lamp should be lit the moment the supply is on. No lamp means brown/blue, not the safety circuit.
  2. Receiver powered? Same check on the receiver's own supply pair.
  3. Alignment and synchronisation. A receiver that never goes green with a genuinely clear field is usually misaligned or has lost CP. Confirm the black conductors of the two sticks are joined, then align — the DQC tolerates an incidence angle of ±5° at 10,000 lux, so a stick rotated in its bracket will not lock on.
  4. Reset mode. If the relay is strapped for automatic restart it will never respond to a button, and if it is strapped for manual it will never restart on its own. Confirm which mode the strapping actually selects before suspecting the button.
  5. Reset contact polarity and edge. Most monitored reset circuits act on the release of the button, not the press. A button held closed, or wired normally-closed into an input expecting a rising edge, produces exactly the "nothing happens" symptom.
  6. EDM loop continuity. With the machine de-energised, check continuity through the normally-closed auxiliary contacts of every contactor in the loop. One contactor left out of the chain, or an auxiliary block that was never fitted, opens the loop permanently. Full worked examples are in EDM feedback wiring examples with series NC contacts.
  7. Welded contactor. If the EDM loop is wired correctly and still open with everything de-energised, a main contact has almost certainly welded — which is precisely the failure EDM exists to catch. See EDM lockout that will not reset. Replace the contactor; do not bridge the loop to clear the fault.
  8. Channel discrepancy. Safety relays require both inputs to change within a short window. If one channel is slow, intermittent or open, the relay latches out. Measure both outputs per the table above.
  9. Cross-fault. An output shorted to +24 V looks permanently "safe to run" to a meter but is detected and latched by the relay. Inspect for crushed cable at cable entries and for a conductor caught under a terminal screw.

XV. Selection Parameters and Recommendations

Verify your requirements against these DQC specifications:

For more industry updates and technical guides, visit our Latest News Section.

Standards this page works to — and who may sign the installation off

Wiring a light curtain correctly is necessary but not sufficient. The documents below govern whether the resulting protective device is actually fit for the risk it is guarding against:

Scope of this guide. These diagrams are educational reference, not an installation instruction for your machine. The manual shipped with your unit takes precedence over anything here wherever the two differ. Commissioning a protective device is work for a competent person: the mounting distance must be recalculated from the measured stopping time of the actual machine, and the completed safety function must be validated before the guard is relied on. De-energise and apply lock-out/tag-out before landing any conductor. DAIDISIKE publishes this guide as the manufacturer of the DQ-series curtains described; it does not constitute a conformity assessment of your installation.

XVI. Summary

Correctly completing the wiring for a safety light curtain is the first step in ensuring workshop safety. Always remember: the CP synchronization wire must not be left floating, the shielded wire must be grounded at a single point, the OSSD channels stay independent, and the EDM loop is what stands between a welded contactor and an unplanned restart.

Free download — Safety Light Curtain Wiring Handbook (PDF)
⬇ Download the PDF

Choose DAIDISIKE (戴迪斯科) — Professional Safety Solutions for Modern Industry.

DAIDISIKE Tech & Video Center

Advanced Sensor Solutions for Industrial Safety and Automation

DAIDISIKE Corporate Profile

Discover our commitment to precision engineering and manufacturing.

Safety Interlock DX Series

Real-world application for advanced machine safeguarding.

AGV LiDAR DLD30T-5N 40

Enhanced perimeter security and collision prevention solutions.

Vehicle DQLV Light Curtains

Optimized for toll stations and weighbridges profiling.

Measuring DQL Series 3D

Dimensional measurement and object positioning principles.

DQC Universal Grating

Installation guide for hand & finger safeguarding.

Waterproof DQR Series

Performance under high-pressure washdowns.

Color Mark Sensors

Intelligent recognition for high-speed packaging lines.

Strip DK-D461 Sensors

Advanced background suppression for irregular shapes.

Area DQSA Protection

Cost-effective side safeguarding using mirror reflection.

OUR PRODUCTSFACTORY TOUROUR TEAMVIDEO CASE STUDIESSOLUTIONS & FAQ

Frequently Asked Questions

What do the wire colours mean on a DQC 5-core safety light curtain cable?

On a typical DQC 5-core cable each core has a defined function — supply positive, supply negative (0 V), the OSSD output or outputs, and a shield or ground (often yellow-green). Always confirm the exact colour-to-function mapping against the specific model's datasheet before wiring.

How do I wire the transmitter and receiver?

The transmitter generally needs power and the synchronisation lines; the receiver carries the OSSD safety outputs that go to the safety relay or controller. Supply 24 V DC to both, follow the model's pin assignment, and keep the shield connected as specified.

How do you wire a safety light curtain to a safety relay?

Feed the curtain from 24 VDC through a 5 A fuse, take OSSD1 and OSSD2 into the relay's two safety inputs (S1/S2) on separate fuses and separate routing, wire the contactors' NC auxiliary contacts in series back into the EDM input, and choose the reset mode at the SR/SRC terminals — shorted for automatic reset, open with a momentary button for manual reset.

What is the OSSD output on a light curtain?

OSSD (Output Signal Switching Device) is the curtain's safety-rated solid-state output pair. Both channels switch off when a beam is interrupted, and the downstream safety relay cross-monitors them so that a short between the channels or a stuck channel is detected. That is why OSSD1 and OSSD2 must never be merged into a single input.

Can I connect a safety light curtain directly to a standard PLC?

Only for monitoring. A standard PLC (e.g. FX5U or S7-1200) may read OSSD status, EDM state and reset requests for diagnostics and HMI display, but it must never perform the safety stop itself — the stop path has to run through a safety relay or safety controller with force-guided contacts.

What is the difference between NPN and PNP light curtain wiring?

An NPN output sinks current, so the load sits between the positive supply and the output; a PNP output sources current, so the load sits between the output and 0 V. Input commons follow the same split — PNP blocks common to 24 V+, NPN blocks common to 0 V — and mixing the two polarities on one input common causes phantom or intermittent input states.

Why does my light curtain trip randomly?

The usual wiring causes are signal cables routed in the same tray as VFD or motor power (keep ≥ 200 mm separation and cross at 90°), a shield left floating or grounded at both ends (use a single-point ground), or a synchronization line left unconnected. Check routing and grounding before suspecting the curtain itself.

Why is the shielded (yellow-green) wire important?

The shield drains electrical noise to ground, which helps prevent interference-related nuisance trips, especially near welding or variable-speed drives. Connecting it as the manual specifies is part of achieving stable, reliable operation.

What should I check before powering on?

Confirm supply voltage and polarity, that the OSSD channels are wired to the correct inputs, that the shield is connected, and that connectors are secure. A pre-power check against the wiring diagram prevents damage and helps the safety function work on the first test.

How do I select the right parameters for my application?

Match resolution to the hazard (finger, hand or body protection), height to the opening, and range to the operating distance with margin, then confirm the safety level against the risk assessment and validate the mounting distance to ISO 13855.