中文官网
APPLICATION CASE · PRESS SAFEGUARDING · 2026-06-14 · Content updated: 2026-09-06

Safeguarding a Mechanical Press: Why Two-Hand Control Alone Is Not Enough, and How a Type 4 Light Curtain Closes the Gap

A representative, unvalidated power-press scenario: two-hand control protects its user, not every person who can approach the dies. Other access needs an assessed safeguard. This example considers a suitable Type 4 light curtain only where the press can reach a safe state in time and the applicable machine requirements permit its use.

DQC light-curtain product illustration, not a validated press installation
DQC product illustration only. Its current page does not publish a Type/PL rating; do not treat this image as a Type 4 press installation.

The representative cell: one operator, one open side, two different hazards

This is a representative power-press cell — not a named customer, tested installation or measured performance claim. An operator stands at a fixed station and runs the press from a Type IIIC two-hand control: two guarded buttons that must be pressed concurrently and synchronously to initiate the slide. Its positioning and sustained-actuation behavior must be validated for the press so that releasing an actuator cannot allow access before the hazard reaches the required safe state.

The problem is the other side. The point of operation also faces an open loading and inspection plane where a second worker — a loader, a helper, a QC inspector — can approach and reach toward the dies. The two-hand control on the operator's station does nothing to stop a stroke the operator legitimately initiates while that second person's hand is in the die area. That open access plane is exactly what a suitable guard or protective device must address. Assess the press photoelectric-guard application limitsbefore selecting an ESPE arrangement.

Two-hand control: assessed operator task
Access safeguard: other reachable routes
E-stop: complementary emergency function

↓ Separate compatible safety inputs ↓

Validated safety logic and restart prevention

↓ Monitored final elements / press control ↓

Required press safe state — demonstrated stopping capability

Concept only: no raw OSSD joining, generic muting input or assumed DA31 compatibility.

Conceptual safety-function architecture, not a terminal diagram. Each device needs its own compatible evaluation; the architecture and final elements must achieve the required common safe state.

Why is two-hand control alone insufficient when others are nearby?

This is the load-bearing point of the whole case, and it comes straight from the standard. ISO 13851 explicitly states a two-hand control device only offers protection for the person using it. A two-hand control forces both of the operator's hands onto actuators away from the danger zone, so neither of their hands can be in the point of operation during the stroke. That is the entire scope of its protection. It has no way to know whether anyone else is near the dies.

A second person's access must be addressed, but the standard does not automatically demand a light curtain in every case. Fixed or interlocked guards or other permitted devices may be appropriate. In the United States, OSHA 1910.217 prohibits presence-sensing protection on full-revolution clutch presses; additional control-reliability and brake-monitor requirements also apply in its stated cases. A light curtain cannot make an ineligible press stoppable.

Design review question: Who can reach the dies, in each operating mode, while another person initiates a stroke? Record the access routes, the safe-state requirement and the device that prevents or detects each route. Do not use the operator's two-hand station as evidence that another worker is protected.

The standards, and what each one actually governs

It helps to keep the lanes straight, because each standard answers a different question:

Standards and legal obligations have different roles. Check the exact applicable national adoption and market conformity route rather than asserting that IEC publication alone grants, or rules out, presumption of conformity. The safety assessment and documented device evidence remain necessary.

How do you calculate where the light curtain goes? S = K·T + C

The following is simplified distance notation, not the complete ISO 13855:2024 procedure. Select the applicable approach case first:

S = K · T + C

Use the model's documented detection capability, not beam pitch. Under the stated example expression, d = 14 mm gives C = 0 and d = 30 mm gives C = 128 mm. These are arithmetic illustrations, not complete mounting distances or universal body-part thresholds.

We are deliberately not publishing a single computed S for this fictional press — T depends on the real machine's measured stopping time. Use the formula and your own measured numbers. For a full worked method, see our ISO 13855 safety-distance guide.

What does the resolution table look like? (the C term, side by side)

Detection capability dIllustrative access classC = 8·(d − 14) mmTypical use
14 mmFinger0 mmFine reach-in; all other distance and geometry checks still apply
30 mmHand128 mmLarger intrusion allowance in this limited example; other controlling distances may make the final position unchanged
> 40 mmLeg / bodyDo not apply this C expression; select the proper approach casePerimeter / whole-body access guarding

A wrong detection-capability assumption invalidates the distance calculation. Also assess reaching over, under and around the field, and whether a person can pass through and remain undetected.

The other three ways a hand gets in: reach-over, reach-under, reach-around

A vertical curtain only guards the plane it covers. ISO 13855 height tables and good installation practice close the rest:

Each of these defeats the curtain while it still reports “guarded.” They are installation failures, not device failures — and they are entirely on the integrator to get right.

The convergence point: validated safety logic and final-element monitoring

Both protective paths must command the required press safe state through appropriately evaluated safety inputs and validated logic. Select a safety relay or controller architecture by supported input types, required functions and final-element monitoring. Do not connect two devices to one OSSD input pair or assume a DA31 accepts two-hand, ESPE, reset, E-stop and muting functions together without its manual.

Final-element monitoring must match the design.An EDM feedback loop can detect a failure of suitable contactors before restart when implemented as specified. Press clutch/brake monitoring may require additional measures; a generic EDM label is not enough. Establish the monitoring and restart functions from the selected controller and press documentation. DA31 capabilities remain unconfirmed for this combined architecture.

DAIDISIKE relay product illustration; combined input and monitoring compatibility requires documentation
Relay product illustration, not a wiring approval. Verify the exact model's supported inputs, reset and monitoring; the diagram does not establish DA31 compatibility.
Two-hand control principle: synchronous dual-button actuation and release-to-stop behavior for a suitably stoppable press
Two-hand-control principle only, for a suitable stoppable press. It is not the complete safety circuit; actuator position, anti-defeat, stopping behavior and protection of other people require validation.

Where DAIDISIKE products fit this cell

Framed vendor-neutrally, by role — no invented specs:

The close-to-run sequence and the failure modes it tolerates

Functionally the system behaves like this:

  1. Operator presses both buttons concurrently and synchronously (≤ 0.5 s tolerance) → two-hand path permits a stroke.
  2. The curtain field over the open access plane must be clear → OSSD high. A broken field prevents a stroke regardless of the buttons.
  3. Separate evaluated inputs satisfy the validated safety logic; only then can the designed machine-control sequence permit a cycle.
  4. The specified test piece interrupts the field → protective outputs change state → safety logic commands the final elements → the hazard reaches its required safe state within the total time T used for distance S.
  5. The required final-element checks and deliberate restart arrangement must be satisfied. Clearing the field or operating reset alone must not initiate hazardous motion.

Validate the fault behavior required by the assessment: actuator faults, wiring shorts, loss of supply, optical faults and final-element failures. Category 3 and Category 4 are not interchangeable promises that every fault is detected before the next demand. Document the complete architecture and tests, including stopping performance and prevention of unexpected restart.

Common mistakes engineers make on this exact cell

  1. Assuming two-hand control = full safeguarding. It protects its user; other reachable routes require suitable guards or protective devices selected for the press.
  2. Mounting the curtain too close — forgetting that T in S = K·T + C includes the press's own stopping time, not just the curtain response.
  3. Wrong K or wrong C / wrong resolution — using an approach constant outside its allowed case, or substituting beam pitch for documented detection capability.
  4. Reach-over / reach-under / reach-around defeats — reachable gaps above, below or beside the detection field.
  5. No EDM / no monitored final elements — a welded contactor goes undetected and drops the realized PL.
  6. Muting/blanking abuse — muting the curtain to feed material instead of designing it per IEC 62046 re-opens the bystander hazard.
  7. Using a Type 2 curtain, or a laser scanner where a vertical curtain is required — Type 2 caps at ~PLc; a horizontal LiDAR zone does not protect a vertical reach-in plane.
  8. Two independent stops with no common safe state — both paths must achieve the required safe state; a stroke must be impossible while the curtain field is broken.

How does this compare to other brands' kit?

Cross-brand purchasing does not approve a combined architecture. Compare exact two-hand, ESPE and controller documents and the required functions; family names do not establish interchangeable inputs or PL. The Pilz PNOZ alternativesand Allen-Bradley Guardmaster alternativespages are candidate-review guides, not certificates for this cell.

DAIDISIKE production facility manufacturing safety light curtains and safety relays in Foshan, China
DAIDISIKE factory image. The scenario is illustrative, not an installed DQC/DA31 press project.

The takeaway

Begin with the press type, stopping capability and every reachable access route. Where a light curtain is permitted and suitable, validate its field, distance and control chain alongside the operator's two-hand function. Use exact device evidence and controlled validation, not an assumed DQC/DA31 pairing. This scenario has no measured press stop time and is not ready-to-wire guidance.

Primary sources and scope

ISO 13851:2019 addresses two-hand devices, not which machine must use a given Type. OSHA 1910.217supplies the cited US mechanical-press requirements. ISO 13855:2024and IEC 62046:2026address positioning and protective-equipment application; consult the actual texts and applicable machine-specific standard.

Frequently asked questions

Why is two-hand control alone not enough to safeguard a mechanical press?

Two-hand control protects its user, not a second person who can reach the dies. Other access needs suitable guarding selected by the risk assessment and applicable press requirements; a light curtain is not automatically mandatory. First establish press eligibility and stopping capability. OSHA 1910.217 prohibits presence-sensing protection on full-revolution clutch presses in its US scope.

What is a Type IIIC two-hand control device under ISO 13851?

Type IIIC is a two-hand-control classification with synchronous actuation, monitoring and defined fault behavior. The familiar 0.5 s actuation window is only one requirement; anti-defeat, reinitiation, positioning and the complete function also matter. ISO 13851 does not itself specify which machines or applications must use a particular Type.

How do you calculate where to mount the light curtain on a press (ISO 13855)?

Select the applicable ISO 13855:2024 approach case, the device manual and any machine-specific requirements. Include the complete worst-case stopping chain and assess all reach and bypass routes. S = K·T + C and C = 8·(d−14) are simplified examples with defined limits, not a universal press-distance certificate.

What resolution light curtain do I need, and how does it change the safety distance?

Use the documented detection capability and the required access geometry, not nominal beam pitch. Under the limited d≤40 mm example, 14 mm gives C=0 and 30 mm gives C=128 mm, but these are not complete distances. Reaching over, under or around and entry followed by remaining inside need additional assessment.

Why a Type 4 light curtain and not a Type 2 one for a press?

A high-integrity press function can require a documented Type 4 light curtain; Type 2 must not replace it where its capability is insufficient. Determine the required performance from the assessment and applicable press standard. Device Type alone does not prove the complete function's PL/SIL or make an unsuitable press stoppable.

What does the safety relay do, and why is EDM essential?

Safety logic evaluates each protective input and commands the required safe state through suitable final elements. Monitoring must detect the failures required by the design; an EDM loop is one model-specific method and does not replace press brake/control monitoring. Do not assume that DA31 supports the combined two-hand, curtain, reset and monitoring functions without its exact manual.

Can a safety laser scanner (LiDAR) replace the vertical light curtain on the press?

A horizontal scanner field is not equivalent to fine vertical reach-in protection at the dies. A separate area or AGV task needs its own safety assessment and approved scanner configuration. DLD is non-safety perception. ST27 is Type 3, PL d, SIL 2, but that does not establish suitability for the press's point-of-operation function.

Is muting or blanking the press curtain to feed material safe?

Only consider supported functions where the machine-specific assessment and applicable requirements permit them. Apply the relevant IEC 62046:2026 requirements, prevent access through any exempted region and validate the entire sequence. Do not mute or blank merely to feed material or suppress nuisance trips; no such configuration is approved by this scenario.

Safeguarding a press point of operation? Send Foshan DAIDISIKE Optoelectronics Technology Co., Ltd. the press type, manuals, stopping-time record, access layout and required safety functions. A candidate proposal still needs exact model documentation and qualified validation; no Type 4 DQC rating or DA31 combined-function approval is claimed by this article.

Contact DAIDISIKE — +86 15218909599

This is a representative engineering application scenario, not a named customer, plant or project. Brand names (SICK, Banner, Pilz, Allen-Bradley, Guardmaster, IDEC) are the trademarks of their respective owners and are used here only for nominative comparison. This article is general engineering guidance, not a substitute for a competent machine-safety risk assessment. Confirm the ESPE type, resolution, approach speed, measured stopping time and the ISO 13855 distance for your specific press before installation.